- Tel: 0086-21-35324116
- E-mail: sales@shenglincooling.com
References


Country: Indonesia
Application:data center
Cooling capacity: 36.7kW
EER: 3.96
Air volume: 12750m3/h
Refrigerant: R410A
Power supply: 380V/3P/50Hz
Country: Philippines
Application: MRI room in hospital
Cooling capacity: 29.8kW
Electric heating: 11kW
Air volume: 7500m3/h
Refrigerant: R407C
Power supply: 400V/3P/60Hz
Downflow air supply


Country: Tajikista
Application: data base station
Cooling capacity: 13.1kW
Air volume: 2400m3/h
Refrigerant: R407C
Power supply: 380V/3P/50Hz
Country:China
Application: wind farm
Cooling capacity: 50kW
Air volume: 12000m3/h
Refrigerant: R22
Power supply: 380V/3P/50Hz
Features
- High efficiency.
- Built-in reliability
- Rugged construction
Technical Data
Wall-mounted air conditioning unit performance parameter table |
|||||
Model: GT-HFM- |
35 |
45 |
55 |
70 |
|
Cooling capacity |
kW |
35.0 |
45.0 |
55.0 |
70.0 |
Air volume |
m3/h |
8925 |
11475 |
14025 |
17850 |
External static pressure |
Pa |
150 |
200 |
200 |
200 |
Total inpout power |
KW |
26.7 |
32.3 |
43.55 |
51.75 |
Supply air fan |
Type |
EC fan |
|||
Qty |
2 |
2 |
3 |
4 |
|
Power |
1.65*2 |
2.6*2 |
1.65*3 |
1.65*4 |
|
Electric heating |
Type |
Stainless steel pipe |
|||
kW |
9.0 |
9.0 |
18.0 |
18.0 |
|
Unit noise |
dB(A) |
77 |
80 |
82 |
84 |
Temperature control |
℃ |
18~28 |
18~28 |
18~28 |
18~28 |
Power supply |
— |
3N-380V-50Hz |
3N-380V-50Hz |
3N-380V-50Hz |
3N-380V-50Hz |
Compressor |
Type |
Fully enclosed scroll |
Fully enclosed scroll |
Fully enclosed scroll |
Fully enclosed scroll |
Qty |
2 |
2 |
3 |
3 |
|
Power |
6+7.5 |
7.5+9.5 |
7.5+7.5+4.5 |
9+9+7.5 |
|
Refrigerant |
Type |
R134a |
|||
Way |
Externally balanced thermal expansion valve/electronic expansion valve |
||||
Condensing fan |
Type |
Axial fan |
|||
Qty |
2 |
2 |
2 |
3 |
|
Power |
0.45*2 |
0.55*2 |
0.55*2 |
0.55*3 |
|
Drain pipe |
— |
DN25 |
DN25 |
DN25 |
DN25 |
Dimensions |
L(mm) |
1620 |
2120 |
2620 |
3020 |
W(mm) |
900 |
900 |
1000 |
1100 |
|
H(mm) |
2450 |
2450 |
2550 |
2550 |
|
Unit weight |
kg |
850 |
1050 |
1200 |
1700 |
Note:
1. Cooling conditions: indoor dry bulb/wet bulb temperature 27/19℃; outdoor dry bulb/wet bulb temperature 35/24℃;
2. Heating conditions: indoor dry bulb/wet bulb temperature 20/—℃; outdoor dry bulb/wet bulb temperature 7/6℃;
3. The air volume, static pressure, power, etc. in the table are standard parameters, which can be designed according to customer requirements, and the input power of the whole machine may change;
4. The noise is measured at a height of 1.2m and 2m from the front of the unit when cooling under standard air volume;
5. Inverter compressor system can be used to achieve more accurate capacity control;
6. Heaters, humidifiers, hot and cold water coils are optional parts, and specific forms can be configured according to customer site requirements.