- Tel: 0086-21-35324116
- E-mail: sales@shenglincooling.com
Introduction
Liquid-to-Liquid Coolant Distribution Unit CDU, Installed in the cabinet. It is a core cooling device designed for high-density heat dissipation requirements, achieving efficient heat exchange through liquid circulation. Its core function is to absorb the heat of IT equipment through the coolant on the secondary side, and then transfer the heat to the outside through the external cooling system on the primary side such as chilled water, natural cold sources, etc., thereby maintaining the operation of IT equipment within a safe temperature range
Performance Range
· Heat Transfer Capacity:350~1500kW
Product characteristics
(1)Precise control
· Liquid cooling intelligent control system, featuring temperature monitoring, PTpressure monitoring, flow detection, water quality monitoring, and anti-condensation control, with the highest temperature control accuracy reaching +0.5℃
(2)High energy efficiency
(3)High compatibility
(4)High reliability
TECHNICAL PARAMETER(1)
Technical Parameter Table of Distributed CDU Standard Conditions
|
|||||
Indoor unit model
|
CDU200WH2SP
|
CDU250WH2SP
|
CDU300WH2SP
|
CDU350WH2SP
|
CDU400WH2SP
|
code
|
80040017
|
80040023
|
80040016
|
80040024
|
80040015
|
Power supply
|
380VAC/3Ph-50Hz
|
||||
Performance parameters of the unit
|
|||||
Primary side operating
condition
|
35℃/45℃
|
35℃/45℃
|
35℃/45℃
|
35℃/45℃
|
35℃/45℃
|
Secondary side
operating condition
|
40℃/50℃
|
40℃/50℃
|
40℃/50℃
|
40℃/50℃
|
40℃/50℃
|
Heat exchange
capacity-kW
|
200 | 250 | 300 | 350 | 400 |
Primary side flow
rate-m³/h
|
17.2
|
21.5
|
25.8
|
30.1
|
34.4
|
Secondary side flow
rate-m³/h
|
18.7
|
23.4
|
28.1
|
32.0
|
37.5
|
The rated power of the unit is-kW
|
3.2
|
3.2
|
4.2 | 5.8 | 5.8 |
Primary side medium |
Softened water, ethylene glycol solution
|
||||
Secondary side medium | deionized water, ethylene glycol solution and propylene glycol solution | ||||
Device Performance Parameters
|
|||||
The number of circulating pumps
|
1 | 1 | 1 | 1 | 1 |
Available head -m
|
28 | 28 | 28 | 28 | 28 |
Number of heat exchangers
|
1 | 1 | 1 | 1 | 1 |
Size and specification of the connecting pipe
|
|||||
Primary side pipeline | DN50 | DN50 | DN50 | DN80 | DN80 |
Secondary side pipeline | DN50 | DN50 | DN50 | DN80 | DN80 |
Interface type
|
Chuck
|
||||
Primary side Routing Method |
Equipment Underneath Piping
|
||||
Secondary side Routing Method |
Equipment Underneath Piping
|
||||
Unit size and weight
|
|||||
Unit width-mm
|
600
|
600
|
600
|
800 | 800 |
Unit depth-mm
|
1200
|
1200
|
1200
|
1200
|
1200
|
Unit height-mm
|
2000
|
2000 | 2000 | 2000 | 2000 |
Weight-kg
|
400 | 410 | 430 | 510 | 520 |
TECHNICAL PARAMETER(2)
Technical Parameter Table of Distributed CDU Standard Conditions
|
||||
Indoor unit model
|
CDU450WH2SP
|
CDU500WH2SP
|
CDU550WH2SP
|
CDU600WH2SP
|
code
|
80040014
|
80040013
|
80040011
|
80040012
|
Power supply
|
380VAC/3Ph-50Hz
|
|||
Performance parameters of the unit
|
||||
Primary side operating
condition
|
35℃/45℃
|
35℃/45℃
|
35℃/45℃
|
35℃/45℃
|
Secondary side
operating condition
|
40℃/50℃
|
40℃/50℃
|
40℃/50℃
|
40℃/50℃
|
Heat exchange
capacity-kW
|
450 | 500 | 550 | 600 |
Primary side flow
rate-m³/h
|
38.7
|
43 |
47.3
|
51.6
|
Secondary side flow
rate-m³/h
|
42.2
|
46.9
|
51.6
|
56.2
|
The rated power of the unit is -kW
|
5.8
|
7.8
|
7.8
|
7.8
|
Primary side medium |
Softened water, ethylene glycol solution
|
|||
Secondary side medium | deionized water, ethylene glycol solution and propylene glycol solution | |||
Device Performance Parameters
|
||||
The number of circulating pumps
|
1 | 1 | 1 | 1 |
Available head -m
|
28 | 28 | 28 | 28 |
Number of heat exchangers
|
1 | 1 | 1 | 1 |
Size and specification of the connecting pipe
|
||||
Primary side pipeline | DN80 | DN80 | DN80 | DN80 |
Secondary side pipeline | DN80 | DN80 | DN80 | DN80 |
Interface type
|
Chuck
|
|||
Primary side Routing Method |
Equipment Underneath Piping
|
|||
Secondary side Routing Method |
Equipment Underneath Piping
|
|||
Unit size and weight
|
||||
Unit width-mm
|
800
|
800
|
600
|
800 |
Unit depth-mm
|
1200
|
1200
|
1200
|
1200
|
Unit height-mm
|
2000
|
2000 | 2000 | 2000 |
Weight-kg
|
530 |
550
|
570
|
580
|
TECHNICAL PARAMETER(3)
Technical Parameter Table of Distributed CDU Standard Conditions
|
||||
Indoor unit model
|
CDU320WR2SP
|
CDU400WR2SP
|
CDU600WR2SP
|
CDU800WR2SP
|
code
|
80040006
|
80040004
|
80040035
|
80040040
|
Power supply
|
380VAC/3Ph-50Hz
|
|||
Performance parameters of the unit
|
||||
Primary side operating
condition
|
35℃/41℃
|
35℃/41℃
|
36℃/41℃
|
20℃/28℃
|
Secondary side
operating condition
|
40℃/46℃
|
40℃/46℃
|
40℃/45℃
|
33℃/40℃
|
Heat exchange
capacity-kW
|
320 | 400 | 600 | 800 |
Primary side flow
rate-m³/h
|
46.5
|
58.2
|
103.5
|
86.2
|
Secondary side flow
rate-m³/h
|
45.5
|
58.2
|
103.5
|
106.0
|
The rated power of the unit is -kW
|
6.5
|
8.5
|
16.5
|
24.5
|
Primary side medium |
Softened water, ethylene glycol solution
|
|||
Secondary side medium | deionized water, ethylene glycol solution and propylene glycol solution | |||
Device Performance Parameters
|
||||
The number of circulating pumps
|
1 | 1 | 1 | 2+1 |
Available head -m
|
28 | 28 | 28 | 28 |
Number of heat exchangers
|
1 | 1 | 1 | 2 |
Size and specification of the connecting pipe
|
||||
Primary side pipeline | DN80 | DN80 | DN125 | DN100 |
Secondary side pipeline | DN80 | DN80 | DN125 | DN100 |
Interface type
|
Chuck
|
Chuck
|
Flange
|
Flange
|
Primary side Routing Method |
Piping Beneath Equipment
|
|||
Secondary side Routing Method |
Equipment Underneath Piping
|
|||
Unit size and weight
|
||||
Unit width-mm
|
1400
|
1400
|
1600
|
1200 |
Unit depth-mm
|
1000
|
1000
|
1200
|
1200
|
Unit height-mm
|
2200
|
2200 | 2200 | 2200 |
Weight-kg
|
300 |
400
|
700
|
800
|
1、CORE COMPONENTS
High-efficiency variable frequency pump
|
|
![]() |
|
Plate heat exchanger
|
Flowmeter
|
![]() |
![]() |
Temperature sensor
|
Pressure sensor
|
![]() |
![]() |
2、Water quality monitoring sensor(Select accessories)
Select accessories | function |
Backup of temperature and pressure sensors | Participate in the backup of control points to ensure system stability |
Conductivity sensor | Monitor the electrical conductivity of the liquid in the pipeline in real time to determine the purity or composition changes of the liquid |
PH sensor | Monitor the pH level of the coolant in the pipeline in real time to prevent excessive acidity from accelerating metal corrosion and excessive alkalinity from causing scaling |
Total hardness sensor | Monitor the total hardness of the coolant in the pipeline in real time, that is, the total concentration of calcium and magnesium ions in the water, to soften the water in time for treatment and prevent scaling |
Turbidity sensor | Monitor the turbidity of the liquid in the pipeline in real time to reflect the content of suspended particulate matter in the liquid |