Tube Bundle Air Cooler
Shenglin Cooling is one of the toppest Fin Fan Cooler Tube Bundle,Air Fin Cooler Tube Bundle,Air Cooler Tube Bundle in China.During these years of exporting , Shenglin Cooling now has rich experience in the worldwide markets
  • Informations
  • References
  • Air vs. Water

Introduction

The Air Cooler Tube Bundle is the core heat exchange component of an Air Cooled Heat Exchanger, consisting of finned tubes, tube sheets, baffles, and headers. It enables efficient heat transfer between process fluids inside the tubes and ambient air outside. The bundle is designed for easy removal, inspection, and replacement, ensuring long service life and stable performance in demanding industrial applications.


Technical Specification

Item Specification Range Options / Notes
Tube Material Carbon steel, stainless steel, coppebrass, titanium, alloy steel ASTM A179, A210, A214, 304/316/321 SS, duplex SS, etc.
Tube Outer Diameter (OD) 12.7 mm – 38 mm (1/2" – 1 1/2") Customized sizes available
Tube Wall Thickness 1.0 mm – 3.0 mm According to design pressure
Tube Length Up to 12 m Special designs on request
Tube Type Plain, finned, internally enhanced Fin type: L, G, embedded, extruded
Tube Sheet Material Carbon steel, stainless steel, alloy steel Forged or rolled plate
Tube Sheet Thickness 20 mm – 100 mm According to design pressure
Bundle Configuration
Single-pass / Multi-pass U-tube or straight tube
Baffles
Segmental, rod, or customized Improve turbulence & heat transfer
Design Pressure
Up to 10.0 MPa (100 bar) Higher available on request
Design Temperature
-40°C to +400°C With alloy tubes up to higher ranges
Fin Height 8 mm – 16 mm Aluminum, copper, or SS fins
Fin Pitch 250 – 450 fins/m According to cooling requirements
Standards / Codes ASME, TEMA, API 661, ISO 16812 CE, PED certification available
Maintenance Removable bundle Easy cleaning & replacement


Applications

(1)Power plants – turbine & generator cooling

(2)Oil & gas – compressor, LNG, and pipeline station cooling

(3)Petrochemical & refining – process fluid cooling & condensing

(4)Chemical & metallurgy – process heat exchange

(5)Data centers & industrial HVAC – dry cooling solutions


Advantages
● Eco-Friendly: Zero water consumption, no wastewater discharge.
● Cost-Effective: Lower operational and maintenance costs vs. water-cooled systems.
● High Adaptability: Performs reliably in extreme temperatures and harsh conditions.
● Compact Design: Modular structure for space-saving installations.
Long Lifespan: Corrosion-resistant materials and robust engineering.

Optional Configurations
Compliance with ASME and API 661 standards
Forced Draft or Induced Draft fan arrangements
Horizontal or Vertical air flow design

● Smart Controls (temperature sensors, variable speed fans)
● Explosion-Proof, Low-Noise, or Marine-Grade Designs
● Dry/Wet Hybrid System for Enhanced Performance in high ambient temperatures
● Custom painting & corrosion protection

Extended Surface Fin Types Available
L-foot fin (basic embedded fin, economical and widely used for general-purpose cooling)
● Overlapped L-foot fin (LL type): provides better corrosion resistance by overlapping fin foot over the tube surface
Embedded G-fin: fins mechanically embedded into the tube surface for improved thermal contact and durability
● Knurled L-foot fin (KL type): uses a knurled surface on the tube to enhance mechanical bonding between fin and tube
Extruded fin: formed by extruding aluminum over the tube for maximum corrosion resistance and strength, ideal for harsh environments
Bimetallic finned tubes: e.g., aluminum fins on carbon steel or stainless steel tubes, combining thermal conductivity with structural or corrosion benefits
● Custom fin materials and geometries available upon request

Header Types Available

● Plug-type header (for compact or low-cost design)
● Removable cover plate header (for easy inspection and maintenance)
● Removable bonnet-type header (for higher-pressure applications with external access)
● Manifold-type header (for multi-pass or special flow arrangements)

Country: Singapore
Standard: ASME & API 661
Main Material: SS304 Tube/Alu. Fins




Country: Thailand
Main Material: Carbon Steel Tube /Alu. Fins




Country: China
Main Material: Cu Tube and Alu. Fins
Engine Rating: 4000KW /unit




Country: the Philippines
Main Material: Copper Tube/Alu. Fins
Application: Diesel Generator Radiator




Country: China

Caterpillar Engine




Country: Oman
Cooling Capacity: 1.4MW/units
Main Material: Copper Tube/Alu. Fins




Country: Russia
Standard: ASME & API 661
Main Material: SA-213 TP304 Tube / Alu. Fins




Country: USA
Main Material: Carbon Steel Tube /Alu. Fins




Country: Sri Lanka
Main Material: Carbon Steel Tube /Alu. Fins

Air-Cooled vs. Water-Cooled Heat Exchangers

Which One to Choose?

Air-cooled systems are recommended for water-scarce or high-temperature regions, offering low maintenance costs and zero water consumption.

Water-cooled shell-and-tube exchangers are ideal when lower outlet temperatures, compact installation, or reliable water supply are required.

We also offer hybrid (dry/wet) air-cooled systems for enhanced performance in hot climates.

Supporting Products:


Air Fin Cooler / Dry Cooler
Shell and Tube Heat Exchanger
Plate Heat Exchanger
Hybrid Cooling Systems (Dry + Spray)

Air-Cooled Heat Exchangers (Dry Coolers, Air Fin Coolers)
Advantages

Environmentally friendly: no water consumption, no thermal or chemical pollution

Site flexibility: suitable for arid areas or water-scarce regions

Easy maintenance: corrosion-free, scaling-free, long service life

Lower operating costs: air has low resistance and no treatment cost

Passive cooling: retains 30–40% natural cooling even when power is off


Limitations

Cooling is limited by dry-bulb temperature; it cannot cool below ambient

Requires a larger footprint due to low air-side heat transfer

Affected by weather: wind, sunlight, and seasonal changes impact performance

Noise: due to fans and airflow

Requires finned tubes and specialized fan systems


Shell-and-Tube Water-Cooled Heat Exchangers
Advantages

High cooling efficiency: outlet temperature can approach wet-bulb conditions

Compact design: smaller footprint, easily integrated into tight spaces

Stable performance: unaffected by ambient temperature fluctuations


Quiet operation: no fans, minimal noise

Limitations

High water consumption and pollution risk

Needs water source, pumps, pipelines, and treatment systems

Corrosion & scaling: frequent maintenance and chemical treatment required

Total shutdown upon power failure

Biological growth risk in warm climates