Air Conditioner For Energy Storage Container
As the best China Air Conditioner For Energy Storage Container supplier, provides quality Air Conditioner For Energy Storage Container to global clients .
  • information

References

Country: Indonesia

Application:data center

Cooling capacity: 36.7kW

EER: 3.96

Air volume: 12750m3/h

Refrigerant: R410A

Power supply: 380V/3P/50Hz

Country: Philippines

Application: MRI room in hospital

Cooling capacity: 29.8kW

Electric heating: 11kW

Air volume: 7500m3/h

Refrigerant: R407C

Power supply: 400V/3P/60Hz

Downflow air supply


Country: Tajikista

Application: data base station

Cooling capacity: 13.1kW

Air volume: 2400m3/h

Refrigerant: R407C

Power supply: 380V/3P/50Hz


Country:China

Application: wind farm

Cooling capacity: 50kW

Air volume: 12000m3/h

Refrigerant: R22

Power supply: 380V/3P/50Hz

Features

  • High efficiency
  • Built-in reliability.
  • Rugged construction.

Technical Data

Wall-mounted air conditioning unit performance parameter table

Model: GT-HFM-

35

45

55

70

Cooling capacity

kW

35.0

45.0

55.0

70.0

Air volume

m3/h

8925

11475

14025

17850

External static pressure

Pa

150

200

200

200

Total inpout power

KW

26.7

32.3

43.55

51.75

Supply air fan

Type

EC fan

Qty

2

2

3

4

Power

1.65*2

2.6*2

1.65*3

1.65*4

Electric heating

Type

Stainless steel pipe

kW

9.0

9.0

18.0

18.0

Unit noise

dB(A)

77

80

82

84

Temperature control

1828

1828

1828

1828

Power supply

3N-380V-50Hz

3N-380V-50Hz

3N-380V-50Hz

3N-380V-50Hz

Compressor

Type

Fully enclosed scroll

Fully enclosed scroll

Fully enclosed scroll

Fully enclosed scroll

Qty

2

2

3

3

Power

6+7.5

7.5+9.5

7.5+7.5+4.5

9+9+7.5

Refrigerant

Type

R134a

Way

Externally balanced thermal expansion valve/electronic expansion valve

Condensing fan

Type

Axial fan

Qty

2

2

2

3

Power

0.45*2

0.55*2

0.55*2

0.55*3

Drain pipe

DN25

DN25

DN25

DN25

Dimensions

Lmm

1620

2120

2620

3020

Wmm

900

900

1000

1100

Hmm

2450

2450

2550

2550

Unit weight

kg

850

1050

1200

1700


Note:
1. Cooling conditions: indoor dry bulb/wet bulb temperature 27/19℃; outdoor dry bulb/wet bulb temperature 35/24℃;

2. Heating conditions: indoor dry bulb/wet bulb temperature 20/—℃; outdoor dry bulb/wet bulb temperature 7/6℃;

3. The air volume, static pressure, power, etc. in the table are standard parameters, which can be designed according to customer requirements, and the input power of the whole machine may change;

4. The noise is measured at a height of 1.2m and 2m from the front of the unit when cooling under standard air volume;

5. Inverter compressor system can be used to achieve more accurate capacity control;

6. Heaters, humidifiers, hot and cold water coils are optional parts, and specific forms can be configured according to customer site requirements.

Application

Applications including energy storage containers, telecommunications shelters, classrooms, relocatable offices and control rooms.
Product Catalog